441H generator backup protection relay

The generator backup protection relay is designed for the protection of thermal and hydroelectric generating units with a capacity of 10 MW or less, and works in conjunction with the AGP-441H differential protection device to provide protection. Its primary scope of protection covers the generator outlet and areas beyond it. It is typically installed in a panel or mounted directly on a switchgear cabinet.

Product Functions (ANSI):27/59/46/32/40/51V/49/87UD/81U/81O/64

Communication Mode:Optional: RS-485, CAN bus, Ethernet, IEC 60870-5-103 (IEC-103)

In-house Factory & Technical Team, OEM ODM Custom Electrical Equipment

Description

Product Overview

  • Generator backup protection relay is designed for the protection of thermal and hydroelectric units with a capacity of 10 MW or less, and works in conjunction with the AGP-441H differential protection device to provide protection.
  • The generator backup protection device is generally installed in a centralized panel layout for unified monitoring, protection and logical configuration.
  • The overall protection functions, technical performance and external interface specifications fully comply with international IEC and IEEE standards, ensuring standardized, reliable and consistent protection operation for generator sets under normal and fault conditions.

Product Functions (ANSI)

  • generator composite voltage overcurrent protection|50V
  • Generator transverse differential|87GT
  • generator reverse power protection |32
  • Loss of Field Protection |40
  • Undervoltage Protection|27
  • Underfrequency Protection|81U
  • Overfrequency Protection|81O
  • stator earth fault protection|64
  • Thermal overload protection|49
  • Overvoltage Protection|59
  • Negative Sequence Overcurrent Protection|46
  • VT Circuit Break / VT Failure|60
  • Control Circuit Disconnection|74

Communication Mode

  • Optional: RS-485, CAN bus, Ethernet, IEC 60870-5-103 (IEC-103)

Setting Table

No. Description Setting Range Conversion Factor for Upload & Download
1 Control Word 1 0000~FFFF
2 Control Word 2 0000~FFFF
3 Control Word 3 0000~FFFF
4 Overcurrent Stage 1 Delay 0.00~120.00s ×100
5 Overcurrent Stage 2 Delay 0.00~120.00s ×100
6 Overcurrent Stage 3 Delay 0.00~120.00s ×100
7 Negative Sequence Stage 1 Delay 0.00~120.00s ×100
8 Negative Sequence Stage 2 Delay 0.00~120.00s ×100
9 Transverse Differential Protection Delay 0.00~120.00s ×100
10 Stator Earth Fault Delay 0.00~120.00s ×100
11 Overload Delay 0.00~120.00s ×100
12 Under-voltage Delay 0.00~120.00s ×100
13 Over-voltage Delay 0.00~120.00s ×100
14 Under-frequency Delay 0.00~120.00s ×100
15 Over-frequency Delay 0.00~120.00s ×100
16 Reverse Power Delay 0.00~120.00s ×100
17 Loss of Excitation Time Limit 1 0.00~120.00s ×100
18 Loss of Excitation Time Limit 2 0.00~120.00s ×100
19 Overcurrent Stage 1 Setting (Instantaneous Overcurrent Setting) 1.00~99.99A ×100
20 Overcurrent Stage 2 Setting (Time-limit Instantaneous Overcurrent Setting) 1.00~99.99A ×100
21 Overcurrent Stage 3 Setting (Overcurrent Protection Current Setting) 1.00~99.99A ×100
22 Overload Setting (Overload Current Setting) 1.00~99.99A ×100
23 Spare Setting (Original Start Setting) 1.00~99.99A ×100
24 Transverse Differential Setting 0.02~5.00A ×100
25 Negative Sequence Stage 1 Setting 1.00~99.99A ×100
26 Negative Sequence Stage 2 Setting 1.00~99.99A ×100
27 Under-voltage Blocking Setting (Low voltage setting for blocking overcurrent/frequency protection) 5.00~100.00V ×100
28 Negative Sequence Voltage Setting (Negative sequence voltage setting for blocking overcurrent) 5.00~100.00V ×100
29 Stator Earth Fault Setting 5.00~100.00V ×100
30 Over-voltage Setting (Over-voltage Trip Setting) 0.00~100.00V ×100
31 Under-voltage Setting (Under-voltage Trip Setting) 0.00~100.00V ×100
32 Reverse Power Setting 0.05~0.20 Pn ×100
33 Active Power Blocking Setting for Loss of Excitation 0.05~0.20 Pn ×100
34 Reactive Power Setting for Loss of Excitation 0.05~0.20 Pn ×100
35 Under-frequency Protection Setting 0.20~10.00Hz ×100
36 Over-frequency Protection Setting 0.20~10.00Hz ×100
37~48 Reserved

Outline and Installation Dimensions

Front View Dimension Drawing of the Generator Backup Protection Device Dimension Drawing of the Rear Side of the Generator Backup Protection Device Side Dimension Drawing of the Generator Backup Protection Device Dimensions for Cutouts in Generator Backup Protection Devices

FAQ

Q:What technical parameters should be considered when selecting a backup protection device for a generator?

A:When selecting a backup protection device for a generator, the following factors should be considered:
1. Whether the product meets acceptance standards; 2. The product’s features, including communication methods and protection functions; 3. The product’s installation method and scope of application, which should be determined based on the specific circumstances of the project.

Q:What are the common protection functions of generator backup protection devices?

A:Generator relay protection covers common functions of generator backup systems including overcurrent, loss-of-field, undervoltage, underfrequency and stator ground fault protection; these are standard features among main types of generator protection relays, while other protection functions are configured on a case-by-case basis.

Q: Main protection functions & ANSI codes?

A: 51 overcurrent, 46 negative sequence, 32R reverse power, 24 overexcitation, 21G impedance backup.

2 reviews for 441H generator backup protection relay

  1. xiao zhang

    This generator backup protection relay(21G/46/51/32R/24) integrates overcurrent, negative-sequence, reverse power and overexcitation protections. Adopts voltage restraint logic to avoid maloperation, supports fault recording and multi-protocol communication, ideal for various synchronous generator units.

  2. Jack

    Built-in self-diagnostic features make maintenance much easier.

Add a review

Your email address will not be published. Required fields are marked *

High Quality

Stable performance, reliable design, ensuring safe operation for power system protection and grid stability.

Fast Delivery

Timely delivery to support your urgent orders and project schedules efficiently and professionally at any time.

Best Warranty

Professional Warranty: Reliable after-sales support for stable relay protection and long-term customer satisfaction.