Transformer Differential Protection|87T

Transformer-differential-protection|87t and control units are suitable for substations operating at voltage levels of 110 kV and below. Typically, they are installed in a single panel alongside transformer backup protection devices, non-electrical quantity protection devices, and transformer measurement and control units.

Product Functions (ANSI)

Transformer High-Speed Differential Protection 87T-HI / 87HS

Transformer Differential Protection Relay 87T

CT Open-Circuit Detection and Excessive Differential Current Alarm

Overcurrent-start fan

In-house Factory & Technical Team, OEM ODM Custom Electrical Equipment

 

Description

Product Overview

  • The AST-441H Digital Transformer Differential Protection|87T and Control Unit is suitable for transformer protection in substations with voltage levels of 110kV and below.

Product Functions (ANSI)

  • Transformer High-Speed Differential Protection 87T-HI / 87HS
  • Transformer Differential Protection Relay 87T
  • CT Open-Circuit Detection and Excessive Differential Current Alarm
  • Overcurrent-start fan

Communication Features

  • Communication interfaces (optional): RS-485, CAN bus, Ethernet, IEC 60870-5-103.
  • This transformer differential protection device uploads real-time data such as measurements, waveforms, fault and alarm messages, together with all protection parameters and configurations. It supports remote online setting modification and protection function switching.
  • The device also accepts commands from the master station, including remote control, time synchronization, parameter adjustment and data access.

Event Logging, Fault Recording

  • Event logs cover protection trips and device self-diagnostic faults. They record event type, occurrence time and operating parameters for protection trips, as well as fault type and time for self-test anomalies.
  • Fault records include protection operation time, type and RMS values pre- and post-triggering.
  • Each channel captures 2 pre-fault cycles and 4 post-fault cycles, with 192 sampling points per channel.
  • The SOE stores up to 48 records and fault reports store up to 16 records after power loss.

General Technical Data

No. Parameter Category Core Technical Specification
1 Power Supply & Rated Electrical Parameters 1. Rated control voltage: AC/DC 220 V

2. Power supply ripple coefficient: ≤ 5%

3. Voltage tolerance: -20% to +15%

4. Rated AC current In: 1 A/5 A (specify when ordering)

5. Rated AC voltage: 100 V

6. Rated frequency: 50 Hz (customizable per project requirements)

2 Power Consumption 1. DC power circuit: ≤ 25 VA (normal operation), ≤ 30 VA (device activated)

2. AC voltage circuit: ≤ 1 VA/phase (at 100 V rated voltage)

3. AC current circuit: ≤ 0.5 VA/phase (1 A In), ≤ 1 VA/phase (5 A In)

3 Output Contact Performance 1. DC circuit: 50 W breaking capacity (voltage ≤ 250 V, current ≤ 0.5 A, time constant 5 ± 0.75 ms); allowable make current ≤ 5 A

2. AC circuit: 50 W breaking capacity (voltage ≤ 250 V); maximum allowable make current 5 A

4 Insulation Performance Meets IEC standard requirements for insulation resistance, dielectric strength, and impulse voltage

Working Principle of Transformer Differential Protection

Transformer Differential Protection

Setting Table of Transformer Differential Protection

No. Display Name Range Step Remark
1 High-speed Differential Setting
1.1 High-speed Differential Protection 1/0 Enable(1) / Disable(0)
1.2 High-speed Differential Setting Value 0.40~99.99A 0.01A
2 Differential Protection Setting
2.1 Differential Protection Enable 1/0 Enable(1) / Disable(0)
2.2 CT Broken Circuit Blocking Differential 1/0 CT break blocking function: Enable(1) / Disable(0)
2.3 Differential Current Setting 0.50~99.99A 0.01A
2.4 Restraint Current Setting 0.50~99.99A 0.01A
2.5 Differential Bias Current Setting 0.50~99.99A 0.01A
2.6 CT Broken Circuit Threshold 0.50~99.99A 0.01A
2.7 Harmonic Restraint Coefficient 0.10~0.70 0.01 Second harmonic restraint ratio
2.8 Slope / Ratio Restraint Coefficient 0.30~0.70 0.01
2.9 Balance Coefficient 0.100~1.999 0.001
3 Overcurrent Fan Control
3.1 Overcurrent Fan Start 1/0 Enable(1) / Disable(0)
3.2 Ventilation Time Delay 0.00~999.99s 0.01s
3.3 Fan Start Current Setting 0.5~99.99A 0.01A
4 General Setting
4.1 Motor Differential Mode Selection 1/0
4.2 HV Side Y/△-11 Connection 1/0
4.3 HV Side Y/△-01 Connection 1/0
4.4 Secondary Wiring Mode 1/0 Delta/Y(1) / Y/Y(0)
4.5 Control Circuit Break Alarm 1/0 Alarm enable(1) / disable(0)
4.6 Current Angle Display 1/0
4.7 Secondary Current Rated 1/0 1A input(1) / 5A input(0)
4.8 Inter-tripping C6C7 1/0 High-speed & differential trip C06C07(1)
4.9 Rated Secondary Current 0.50~99.99A 0.01A HV side CT secondary rated current

Outline and Installation Dimensions

Front View Dimension Drawing of the Transformer Differential Protection Device Dimension Drawing of the Rear Side of the Transformer Differential Protection Device Side Dimension Drawing of the Transformer Differential Protection Device Dimensions for Cutouts in Transformer Differential Protection Devices

FAQ

Q:What is the scope of protection provided by a transformer differential protection device?

A:Transformer differential protection primarily protects the internal components of the transformer. When a turn-to-turn short circuit or a phase-to-phase short circuit occurs inside the transformer, the corresponding protection function in the transformer differential protection device will trigger an alarm and trip the circuit.

Q:How to Select a Transformer Differential Protection Device?

A:When selecting a transformer differential protection device for differential protection of transformer and differential protection for transformer applications, three key points should be noted: first, consider the transformer’s capacity, as larger capacity requires more advanced device functions; second, identify whether the transformer is two-winding or three-winding, since the suitable protection device differs by transformer type; third, refer to relevant industry standards and verify compliance with international norms such as IEC and IEEE.

2 reviews for Transformer Differential Protection|87T

  1. xiao zhang

    Transformer differential relay (87T) adopts percentage restraint algorithm, strong anti-CT-saturation capability and CT break lockout. Instant trip for internal winding faults, flexible parameter setting and multi-communication options for all types of distribution & power transformers.

  2. Jack

    Backed by good technical support and documentation — overall a solid choice.

Add a review

Your email address will not be published. Required fields are marked *

High Quality

Stable performance, reliable design, ensuring safe operation for power system protection and grid stability.

Fast Delivery

Timely delivery to support your urgent orders and project schedules efficiently and professionally at any time.

Best Warranty

Professional Warranty: Reliable after-sales support for stable relay protection and long-term customer satisfaction.