Description
Overview of Relay Motor Protection
- The ASD-441H 3-phase Relay Motor Protection is primarily designed to protect motors.It is suitable for high-voltage motors in 3 kV to 35 kV systems,
and serves as bay-level equipment, performing protection, measurement, control, and communication functions.

Product Functions (ANSI)
- Instantaneous Overcurrent Protection 50
- Definite Time Overcurrent & Negative Sequence Overcurrent Protection 51 / 46
- Inverse Time Overcurrent & Inverse Time Negative Sequence Current Protection 51 / 46
- Negative Phase Sequence Voltage Protection 47
- Locked Rotor Protection: Start Locked Rotor & Running Locked Rotor Protection 48
- Thermal Overload Protection 49
- Undervoltage Protection 27
- Overload Protection 51 / 49
- Zero-sequence Overcurrent Protection 50N / 51N
- Overvoltage Protection 59
- Long Start Time Protection / Start Supervision 66
- VT & CT Disconnection Supervision 60
- Control Circuit Break Monitoring 74
Communication Mode
- Optional: RS-485, CAN bus, Ethernet, IEC 60870-5-103 (IEC-103)
Setting Table
| No. | Description | Setting Range | Conversion Factor for Upload & Download |
|---|---|---|---|
| 1 | Control Word 1 | 0000~FFFF | – |
| 2 | Control Word 2 | 0000~FFFF | – |
| 3 | Control Word 3 | 0000~FFFF | – |
| 4 | Running Stall Time (Running Stall Delay) | 0.00~120.00s | ×100 |
| 5 | Starting Stall Time (Starting Stall Delay) | 0.00~120.00s | ×100 |
| 6 | Instantaneous Overcurrent Delay | 0.00~120.00s | ×100 |
| 7 | Negative Sequence Instantaneous Delay | 0.00~120.00s | ×100 |
| 8 | Phase Sequence Reversal Voltage Delay | 1.00~100.00s | ×100 |
| 9 | Under-voltage Protection Delay | 0.00~120.00s | ×100 |
| 10 | Zero-sequence Overcurrent Delay | 0.00~120.00s | ×100 |
| 11 | Overload Delay | 0.00~120.00s | ×100 |
| 12 | Start Delay | 0.00~120.00s | ×100 |
| 13 | Over-voltage Delay | 0.00~120.00s | ×100 |
| 14 | Running Stall Current Setting | 0.04~99.99A / 0.10~20.00A | ×100 |
| 15 | Starting Stall Current Setting | 0.04~99.99A / 0.10~20.00A | ×100 |
| 16 | Instantaneous Overcurrent Setting (During Start-up) | 0.04~99.99A / 0.10~20.00A | ×100 |
| 17 | Inverse-time Overcurrent Setting | 0.50~10.00A / 0.20~2.00A | ×100 |
| 18 | Negative Sequence Instantaneous Current Setting | 0.04~99.99A / 0.10~20.00A | ×100 |
| 19 | Negative Sequence Inverse-time Current Setting | 0.50~10.00A / 0.20~2.00A | ×100 |
| 20 | Spare Setting (Original Start Setting) | – | ×1 |
| 21 | Zero-sequence Overcurrent Setting | 0.02~5.00A / 0.50~99.00A | ×100 |
| 22 | Current Presence Setting | 0.20~5.00A | ×100 |
| 23 | Overload Current Setting | 0.04~99.99A / 0.10~20.00A | ×100 |
| 24 | Rated Current (Long-term Allowable Current of Motor) | 1.00~5.00A | ×100 |
| 25 | τ1 (Time Constant for Inverse-time Overcurrent) | 1.00~100.00s | ×100 |
| 26 | τ2 (Time Constant for Negative Sequence Inverse-time) | 1.00~100.00s | ×100 |
| 27 | Thermal Protection (Thermal Time Constant) | 1.00~100.00s | ×100 |
| 28 | Thermal Alarm Coefficient | 0.01~0.08 | ×100 |
| 29 | Under-voltage Protection Setting | 5.00~100.00V | ×100 |
| 30 | Over-voltage Setting | 5.00~100.00V | ×100 |
| 31 | Running Instantaneous Current Setting | 0.04~99.99A / 0.10~20.00A | ×100 |
| 32 | Overcurrent Setting | 0.04~99.99A / 0.10~20.00A | ×100 |
| 33 | Overcurrent Delay | 1.00~100.00s | ×100 |
| 34 | Current Blocking Setting (Blocking Value for Over/Under-voltage Protection) | 0.04~99.99A / 0.10~20.00A | ×100 |
| 35 | External Auto-start Delay | 0.100~655.350s | ×100 |
| 36~48 | Reserved | – | – |
Outline and Installation Dimensions

FAQ
Q:Relay Motor Protection is primarily designed to protect motors, so how should one choose one?
A:There are many types of motor protection relays, and several principles should be considered when selecting one.
First, motors are classified by voltage rating into low-voltage and high-voltage categories; different voltage ratings require different selection methods.
Second, consider the motor’s capacity; generally, motors with higher capacity have more stringent technical requirements.
Third, refer to the project’s technical specifications.
Q: What is Relay Motor Protection?
A: It refers to protective relays specially designed to monitor motors and guard against overload, short circuit and other faults.
Q: What core functions does Relay Motor Protection provide?
A: It mainly offers overcurrent, earth fault and overload protection to keep motors running safely.
Q: Where is Relay Motor Protection commonly used?
A: It is widely applied in industrial plants, power stations and distribution systems to protect various electric motors.