Description
Product Overview
- Transformer gas and temperature protection consists of three non-electrical protection boards, which primarily provide non-electrical output functions.Usually installed in the same panel with transformer differential protection and transformer backup protection devices.

Product Functions (ANSI)
| No. | Protection Category | Protection Function Name | ANSI Standard Code |
|---|---|---|---|
| 1 | Buchholz / Gas Protection | Light Gas Protection | 71G‑L |
| 2 | Buchholz / Gas Protection | Heavy Gas Protection | 71G‑H |
| 3 | Temperature Protection | Oil Temperature Protection | 26‑O |
| 4 | Temperature Protection | Winding Temperature Protection | 26‑W |
| 5 | Pressure Protection | Pressure Relief / Surge Protection | 63‑P |
Communication Mode
- Optional: RS-485, CAN bus, Ethernet, IEC 60870-5-103 (IEC-103)
General Technical Data
| No. | Parameter Category | Parameter Name | Technical Specification |
|---|---|---|---|
| 1 | Control Circuit Power Supply | Rated Control Circuit Power Supply | DC 220 V / AC 220 V (to be specified when ordering) |
| 2 | Trip & Close Circuit Rating | Rated Trip & Close Operating Current | 0.5–5 A (to be specified when ordering) |
| 3 | Output Contacts Technical Specifications | DC Circuit Breaking Capacity | 50 W (applicable to DC circuit with voltage ≤ 250 V, current ≤ 0.5 A, time constant 5 ± 0.75 ms) |
| 4 | Output Contacts Technical Specifications | Continuous Current Rating (Output Contacts) | ≤ 5 A |
| 5 | Output Contacts Technical Specifications | Maximum Allowable Make Current (DC Circuit) | 5 A (applicable to DC circuit with voltage ≤ 250 V, current ≤ 0.5 A, time constant 5 ± 0.75 ms) |
| 6 | Input Contacts Technical Specifications | AC Circuit Breaking Capacity (Input Contacts) | 50 W (applicable to AC circuit with voltage ≤ 250 V) |
| 7 | Input Contacts Technical Specifications | Maximum Allowable Make Current (AC Circuit) | 5 A (applicable to AC circuit with voltage ≤ 250 V) |
Environmental Conditions
- Operating conditions: –20°C to +70°C, relative humidity 5% to 95% (no condensation or freezing inside the unit)
- Storage: –30°C to +80°C. When no excitation is applied at the extreme temperature limits, the device shall not undergo irreversible changes, and it shall function normally once the temperature returns to normal. Packaged devices shall be stored at an atmospheric pressure of 80–110 kPa (equivalent to an altitude of 2 km or less) and a relative humidity of no more than 85%.
- Transportation: -25°C to +70°C, relative humidity not exceeding 85%;
Status Indicator Descriptions
| Name | Definition | Color | Status | Remark |
|---|---|---|---|---|
| Heavy Gas 1 | Heavy Gas 1 Indicator | Red | Steady On | |
| Heavy Gas 2 | Heavy Gas 2 Indicator | Red | Steady On | |
| Pressure Relief | Pressure Relief Indicator | Red | Steady On | |
| Over-temperature Trip | Over-temperature Trip Indicator | Red | Steady On | |
| Forced Cooling Trip | Forced Cooling Trip Indicator | Red | Steady On | |
| Power | Power Indicator | Red | Steady On | |
| Light Gas 1 | Light Gas 1 Indicator | Red | Steady On | |
| Light Gas 2 | Light Gas 2 Indicator | Red | Steady On | |
| High Temperature | High Temperature Indicator | Red | Steady On | |
| Cooling Loss | Cooling Loss Indicator | Red | Steady On |
Outline and Installation Dimensions

FAQ
Q:Is non-electrical protection the primary protection or the backup protection for a transformer?
A:Generally speaking, non-current-based protection and transformer differential protection are both core forms of protection for transformers and classified as main transformer protection.
Q:What should be done after a trip triggered by transformer gas and temperature protection (non-electrical protection)?
A:First, check the alarm details of transformer gas and temperature protection trips to confirm the inspection scope. Such trips are usually caused by internal transformer faults and require strict caution.











xiao zhang –
This relay integrates Buchholz gas and winding/oil temperature protection, monitors transformer internal abnormal heating and internal arc faults. Simple setting, relay contact output and optional communication for distribution & power transformers.
Jack –
Complete waveform recording, very useful for fault analysis — a solid product.